GD3128 jara Insulation Resistance Tester ni iṣẹ idanwo pipe ti ọpọlọpọ awọn aye idabobo idabobo ati agbara kikọlu ti o dara julọ, eyiti o le ṣee lo lati ṣe idanwo idabobo idabobo ti agbara nla ohun elo itanna foliteji giga ati awọn laini gbigbe ni agbegbe inductive ti o lagbara gẹgẹbi ipin-iṣẹ.Ohun elo naa gba iboju ifọwọkan awọ otitọ, gbogbo data idanwo ati agbara batiri ti han loju iboju kanna ni iwo kan, ati apapo bọtini bọtini ati bọtini jẹ ki iṣẹ naa rọrun pupọ.Olumulo ko nilo lati ṣe akori ọna iṣiṣẹ naa.Tẹ "IRANLỌWỌWỌ" loju iboju lati gbe jade ni ọna iṣiṣẹ, eyiti o le ṣe itọsọna imunadoko olumulo lati ṣiṣẹ ohun elo naa.Ohun elo naa ni iṣẹ ti itusilẹ iyara, eyiti o le ṣe idasilẹ foliteji ti ohun idanwo lẹsẹkẹsẹ laisi iyika itusilẹ afikun.Atẹle foliteji ti ohun elo le ṣe atẹle laifọwọyi foliteji ifiwe ti ohun idanwo naa.Ti foliteji ba kọja 36V, idanwo naa yoo ni idinamọ laifọwọyi, eyiti o le daabobo ohun elo ati awọn oniṣẹ ni imunadoko.
Ohun elo naa gba idii batiri litiumu gbigba agbara nla.Aago idanwo ti ohun elo ṣe igbasilẹ akoko idanwo laifọwọyi ati tọju awọn abajade idanwo pẹlu ọjọ ati akoko.Iboju ifọwọkan le ni irọrun wọle si data itan ti o gbasilẹ.Ni wiwo USB ti o ya sọtọ patapata le gbe data idanwo si PC lailewu.Ohun elo naa ni ipese pẹlu laini idanwo pẹlu idabobo meji ati Layer aabo, ati igi foliteji giga ti ni ipese pẹlu agekuru alligator ti o rọpo ati kio, eyiti o le ṣe deede si awọn aaye idanwo pupọ.Ohun elo naa gba eto ikarahun-Layer ti o lagbara, ati pe ipele aabo ti apoti ita jẹ IP65, eyiti o le ṣe idiwọ ikọlu ọrinrin ati eruku lakoko gbigbe ati ibi ipamọ, ati daabobo ohun elo ni imunadoko lati ijamba.
GD3128 jara ni iwọn jakejado, ipinnu giga, iṣiṣẹ irọrun, agbara ati agbara, deede ati igbẹkẹle, iṣẹ iduroṣinṣin, ati agbara kikọlu ti o lagbara.Ohun elo naa ni idanwo idabobo idabobo (IR);Idanwo itọka polarization (PI);igbeyewo ratio gbigba (DAR);idanwo rampu (RAMP);àlẹmọ igbeyewo (FR, 10S, 20S, 30S, 40S mẹrin awọn aṣayan);igbeyewo foliteji (V);igbeyewo capacitance (uF);idanwo lọwọlọwọ (nA) ati awọn iṣẹ miiran.Ohun elo naa dara fun idanwo idena idabobo ti ohun elo itanna, awọn laini gbigbe ati awọn ohun elo nla miiran labẹ agbegbe ti agbara nla, foliteji giga ati ifisi to lagbara.O jẹ ohun elo ti o wọpọ ati ohun elo ti ko ṣe pataki fun agbara ina, awọn ibaraẹnisọrọ, meteorology, yara kọnputa, aaye epo, fifi sori ẹrọ itanna ati itọju, ati awọn apa ipese agbara ti ile-iṣẹ ati awọn ile-iṣẹ iwakusa.
●O pọju kukuru-Circuit lọwọlọwọ jẹ 7mA.
●Idanwo idabobo idabobo (IR), idanwo atọka polarization (PI), idanwo ipin gbigba (DAR).
●Ipo idanwo Ramp (RAMP), ipo idanwo àlẹmọ (FR), idanwo agbara (uF)
●Iṣẹ atẹle foliteji, ṣe atẹle laifọwọyi foliteji agbara ti ohun idanwo naa.
●Iṣẹ aago idanwo, ṣe igbasilẹ akoko idanwo laifọwọyi.
●Iṣẹ itusilẹ aifọwọyi, laifọwọyi ati yarayara tu idiyele ohun idanwo naa silẹ lẹhin idanwo naa, laisi Circuit itujade ita.
●Aifọwọyi iṣẹ tiipa.
●Iboju awọ ifọwọkan nla.
●Eto ikarahun-Layer meji, to lagbara ati ti o tọ, ipele aabo IP65.
●Ididi batiri litiumu gbigba agbara ti o ga julọ.
●Iṣẹ ipamọ, le tọju awọn ẹgbẹ 1000 laifọwọyi ti data idanwo akoko gidi pẹlu ọjọ idanwo ati akoko ati akoko idanwo.
●Iṣẹ ikojọpọ, ni ipese pẹlu wiwo USB, data igbasilẹ le ṣe gbejade si kọnputa fun itupalẹ iṣiro ti data.
Awoṣe ọja | Ti won won Foliteji | Idabobo Resistance Range | Kukuru Circuit Lọwọlọwọ |
GD3128A | 250V,500V,1kV,2.5kV,5kV | 0.50MΩ ~ 10.0TΩ | ≥7mA |
GD3128B | 250V,500V,1kV,2.5kV,5kV,10kV | 0.50MΩ ~ 20.0TΩ | ≥7mA |
GD3128C | 250V,500V,1kV,2.5kV,5kV,10kV,15kV | 0.50MΩ ~ 30.0TΩ | ≥7mA |
Idabobo Resistance Ibiti ati Yiye
Ti won won Foliteji | Idabobo Resistance Ibinu | Yiye | Akiyesi |
250V | 0.50MΩ~50.0GΩ | ± 5%rdg 3dgt |
|
50.0GΩ~500GΩ | ± 20%rdg ± 3dgt |
| |
500V | 1.00MΩ~100GΩ | ± 5%rdg 3dgt |
|
100GΩ~1.00TΩ | ± 20%rdg ± 3dgt |
| |
1000V | 1.00MΩ~200GΩ | ± 5%rdg 3dgt |
|
200GΩ~2.00TΩ | ± 20%rdg ± 3dgt |
| |
2500V | 1.00MΩ~500GΩ | ± 5%rdg 3dgt |
|
500GΩ~3.00TΩ | ± 20%rdg ± 3dgt |
| |
5000V | 1.00MΩ~1.00TΩ | ± 5%rdg 3dgt |
|
1.00TΩ~10.0TΩ | ± 20%rdg ± 3dgt |
| |
10KV | 1.00MΩ~2.00TΩ | ± 5%rdg 3dgt |
|
2.00TΩ~20.0TΩ | ± 20%rdg ± 3dgt |
| |
15KV | 1.00MΩ~3.00TΩ | ± 5%rdg 3dgt |
|
3.00TΩ~30.0TΩ | ± 20%rdg ± 3dgt |
1 TΩ (Tera ohm)=1000GΩ=1012Ω
1 GΩ (Giga ohm)=1000MΩ=109Ω
1 MΩ (Mega ohm)=1000KΩ=106Ω
Išẹ | Iwọn idabobo idabobo (IR);Iwọn itọka polarization (PI);ipin gbigba (DAR);Ipo idanwo rampu (RAMP);àlẹmọiṣẹ(10S, 20S, 30S, 40S);vodiwọn oltage (V);agbaratancewiwọn(uF);lọwọlọwọ wiwọn(nA) |
Ibi ti ina elekitiriki ti nwa | Batiri litiumu gbigba agbara 6.2Ah |
Ti won won Foliteji | GD3128A: 250V, 500V, 1kV, 2.5kV, 5kV GD3128B: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV GD3128C: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV, 15kV |
O wu Foliteji Yiye | (5%~10%) ± 10V |
Idabobo Resistance Igbeyewo Ibiti | GD3128: 0.50MΩ~10.0TΩ GD3128B: 0.50MΩ~20.0TΩ GD3128C: 0.50MΩ~30.0TΩ |
O wu Kukuru Circuit Lọwọlọwọ | ≥7mA |
Idanwo Atọka Polarization | Bẹẹni |
Igbeyewo Ratio gbigba | Bẹẹni |
Ipo Igbeyewo Ramp | Idanwo ni awọn igbesẹ ti 10% ti foliteji tito tẹlẹ titi foliteji tito tẹlẹ. |
Àlẹmọ Ipo Idanwo | 10S, 20S, 30S, 40S mẹrin yiyan. |
Foliteji Igbeyewo | Ibiti o: AC/DC: 0V~1000V; Yiye: ± 5%rdg± 3V |
Idanwo agbara | Ibiti o: 10nF~25uF; Yiye: ± 10%rdg± 10nF |
Idanwo lọwọlọwọ | Ibiti o: 0.01nA~7mA; Yiye: ± 5%rdg ± 0.5nA |
Foliteji Atẹle | Bojuto awọn foliteji ti awọnidanwod ohun, ati atẹle ipo idasilẹ lẹhin idanwo, ewọ lati ṣe idanwo nigbati foliteji ba kọja 36V, aabo irinse ati oniṣẹ. |
Aago Idanwo | Akoko idanwo igbasilẹ aifọwọyi, timingibiti: 0s ~ 9999s |
Išẹ ipamọ | Fi data idanwo pamọ laifọwọyi pẹlu ọjọ idanwo ati akoko, lapapọ awọn ẹgbẹ 1000 |
Išẹ agberu | Ṣe igbasilẹ data ti o fipamọ sori kọnputa nipasẹ okun ibaraẹnisọrọ USB. |
Ifihan agbara batiri | Pẹlu ifihan agbara batiri, nigbati foliteji batiri kekere yoo leti siidiyelebatiri naa. |
Tiipa aifọwọyi | Lẹhin iṣẹju 15, ibẹrẹ yoo ku laifọwọyi laisi iṣẹ ṣiṣe eyikeyi. |
Iwọn | 280mm × 260mm × 160mm |
Iwọn | 4900g (pẹlu batiri naa) |
Idanwo Wires | Awọ pupa okun idanwo foliteji giga 1pc (pẹlua agekuru alligator ati kio), okun idanwo awọ alawọ ewe 1pc, waya idanwo awọ dudu 1pc |
Ipele Idaabobo | Pa idii IP65, ṣii ọran IP40 |
Ayika Ṣiṣẹ | -20℃~50℃; 80% rh |
Itaja Ayika | -25 ℃~65℃; 80% rh |
Idabobo Resistance | 50MΩ(1000V) (laarin awọn Circuit igbeyewo ati ikarahun) |
Koju Foliteji | AC 3kV50Hz 1 iṣẹju(laarin awọn Circuit igbeyewo ati ikarahun) |
Aabo | IEC61010-1, IEC61326-1 |