GDCO-301 Eto Abojuto Ayelujara ti Yiyi lọwọlọwọ lori apofẹlẹfẹlẹ Cable
Awọn okun ti o wa loke 35kV jẹ awọn kebulu ti o ni ẹyọkan pẹlu apofẹlẹfẹlẹ irin.Niwọn igba ti apofẹlẹfẹlẹ irin ti okun ọkan-mojuto ti wa ni isunmọ pẹlu laini aaye oofa ti ipilẹṣẹ nipasẹ lọwọlọwọ AC ninu okun waya mojuto, awọn opin meji ti okun ọkan-mojuto ni foliteji ti o ga.Nitorinaa, awọn igbese ilẹ ti o yẹ yẹ ki o mu lati tọju foliteji ifasilẹ laarin iwọn foliteji ailewu (nigbagbogbo ko ju 50V, ṣugbọn ko ju 100V pẹlu awọn igbese ailewu).Nigbagbogbo, apofẹlẹfẹlẹ irin ti okun laini kukuru ẹyọkan-mojuto ti wa ni ilẹ taara ni opin kan ati ti ilẹ nipasẹ aafo tabi alatako aabo ni opin keji.Afẹfẹ irin ti laini gigun ti ẹyọkan - okun mojuto ti wa ni ilẹ nipasẹ mẹta - apakan apakan agbelebu - asopọ.Laibikita iru ọna ilẹ ti o gba, idabobo apofẹlẹfẹlẹ ti o dara jẹ pataki.Nigbati idabobo ti okun ba bajẹ, apofẹlẹfẹlẹ irin yoo wa ni ilẹ ni awọn aaye pupọ, eyiti yoo ṣe ina ṣiṣan kaakiri, mu isonu ti apofẹlẹfẹlẹ pọ si, ni ipa lori agbara gbigbe lọwọlọwọ ti okun, ati paapaa fa okun USB lati sun. nitori overheat.Ni akoko kanna, iṣeduro giga foliteji okun irin apofẹlẹfẹlẹ ilẹ taara asopọ aaye tun jẹ pataki pupọ, ti aaye ilẹ ko ba le ni ipilẹ ni imunadoko fun awọn idi pupọ, agbara irin apofẹlẹfẹlẹ okun yoo dide ni didasilẹ si ọpọlọpọ awọn kilovolts paapaa ẹgbẹẹgbẹrun awọn folti. , o rọrun lati ṣe amọna si fifọ apofẹlẹfẹlẹ ita ati itusilẹ ti nlọsiwaju, nfa ilosoke ti iwọn otutu ti okun ita ita tabi paapaa sisun.
GDCO-301 nlo ọna ti n kaakiri lọwọlọwọ.Nigbati apofẹlẹfẹlẹ irin okun ọkan-mojuto wa labẹ awọn ipo deede (ie, ilẹ-ojuami-ọkan), ṣiṣan kaakiri lọwọlọwọ lori apofẹlẹfẹlẹ, ni pataki lọwọlọwọ capacitive, jẹ kekere pupọ.Ni kete ti ilẹ-aye olona-pupọ ba waye lori apofẹlẹfẹlẹ irin ti o si ṣe lupu kan, ṣiṣan kaakiri yoo pọ si ni pataki ati pe o le de diẹ sii ju 90% ti lọwọlọwọ akọkọ.Abojuto akoko gidi ti kaakiri apofẹlẹfẹlẹ irin ati awọn ayipada rẹ le ṣe akiyesi ibojuwo ori ayelujara ti aṣiṣe aaye-pupọ ti ọkan-mojuto USB irin apofẹlẹfẹlẹ, nitorinaa lati rii ni akoko ati ni deede ati rii aṣiṣe aiye, ni ipilẹṣẹ yago fun iṣẹlẹ ti ijamba okun ati rii daju iṣẹ ailewu ati igbẹkẹle.
O nlo GSM tabi RS485 bi ipo ibaraẹnisọrọ.O dara fun ibojuwo aibikita ilẹ-ojuami pupọ ti awọn kebulu mojuto ẹyọkan loke 35kV.
Eto Abojuto Ayelujara GDCO-301 ti Yiyi lọwọlọwọ lori apofẹlẹfẹlẹ Cable pẹlu: ẹyọ akọkọ ti ẹrọ ibojuwo iṣọpọ ati ẹrọ oluyipada lọwọlọwọ, iwọn otutu ati sensọ ole ole.Ayipada iru lọwọlọwọ ti wa ni ti fi sori ẹrọ lori laini ilẹ ti apofẹlẹfẹlẹ USB ati pe o ti yipada si ifihan agbara keji ṣaaju iṣafihan ẹrọ ibojuwo.A ti lo sensọ iwọn otutu lati ṣe atẹle iwọn otutu okun, ati sensọ anti-ole ti a lo lati ṣe atẹle laini ilẹ gbigbe kaakiri.Awọn akojọpọ ti okeerẹ eto ibojuwo ori ayelujara ti apofẹlẹfẹlẹ okun jẹ bi atẹle:
●Abojuto akoko gidi ti lọwọlọwọ ilẹ ti apofẹlẹfẹlẹ USB alakoso mẹta, lọwọlọwọ ilẹ lapapọ ati lọwọlọwọ iṣẹ ti eyikeyi okun akọkọ alakoso;
●Abojuto akoko gidi ti iwọn otutu USB-alakoso mẹta;
●Anti-akoko gidi ibojuwo ole ti ilẹ apofẹlẹfẹlẹ USB;
●Aarin akoko le ṣeto;
●Awọn paramita itaniji ati boya awọn aye ibojuwo ibaramu ni a gba laaye lati ṣe ina itaniji le ṣeto;
●Ṣeto iye ti o pọju, iye to kere julọ ati iye apapọ ni akoko tito tẹlẹ;
●Abojuto akoko gidi ti ipin ti o pọju ati iye ti o kere ju ti lọwọlọwọ ilẹ-alakoso-ọkan laarin akoko iṣiro, ati sisẹ itaniji;
●Abojuto akoko gidi ti ipin ti lọwọlọwọ ilẹ lati fifuye laarin akoko iṣiro, ati sisẹ itaniji;
●Abojuto akoko gidi ti oṣuwọn iyipada ti lọwọlọwọ ilẹ-alakoso-ọkan laarin akoko iṣiro, ati sisẹ itaniji;
●Awọn data wiwọn le ṣee firanṣẹ nigbakugba.
●Le pato ọkan tabi diẹ ẹ sii awọn aye ibojuwo si itaniji, fi alaye itaniji ranṣẹ si foonu alagbeka ti a yan;
●Wiwọn akoko gidi ti foliteji titẹ sii;
●Gbogbo data ibojuwo ni awọn akole akoko lati rii daju iyasọtọ ti data naa;
●Gbogbo awọn sensọ ibojuwo le tunto ni ibamu si awọn ibeere olumulo;
●Awọn atọkun gbigbe data lọpọlọpọ: wiwo RS485, GPRS, GSM SMS, le lo ọkan tabi diẹ sii awọn ipo gbigbe data ni akoko kanna;
●Ṣe atilẹyin itọju latọna jijin ati igbesoke;
●Apẹrẹ agbara agbara kekere, ṣe atilẹyin ọpọlọpọ awọn titẹ sii agbara: CT induction power, AC-DC agbara ati agbara batiri;
●Pẹlu ise ite irinše, pẹlu ti o dara dede & amupu;
●Modular ti o wa ni pipade ni kikun, rọrun lati fi sori ẹrọ, awọn igbese titiipa ni a mu lori gbogbo awọn ẹya, iṣẹ-egboogi-gbigbọn ti o dara, ati rọrun lati rọpo ati pipọ;
●Ṣe atilẹyin ipele aabo IP68.
Nkan | Awọn paramita | |
Lọwọlọwọ
| Ṣiṣẹ lọwọlọwọ | 1 ikanni, 0,5~1000A (le ṣe adani) |
Afẹfẹ ilẹ lọwọlọwọ | 4 ikanni, 0,5~200A (le ṣe adani) | |
Iwọn wiwọn | ± (1%+0.2A) | |
Akoko wiwọn | 5~Awọn ọdun 200 | |
Iwọn otutu | Ibiti o | -20℃~+ 180 ℃ |
Yiye | ±1℃ | |
Akoko wiwọn | 10~Awọn ọdun 200 |
RS485 ibudo
●Oṣuwọn Baud: 2400bps, 9600bps ati 19200bps le ṣeto.
●Ipari data: 8 bit:
●Ibẹrẹ bit: 1 bit;
●Duro die-die: 1 die-die;
●Isọdiwọn: ko si isọdiwọn;
GSM/GPRS ibudo
●Igbohunsafẹfẹ ṣiṣẹ: Quad-band, 850 MHz/900 MHz/1800 MHz/1900 MHz;
●Awọn ifiranṣẹ kukuru GSM Kannada/Gẹẹsi;
●GPRS kilasi 10, Max.download iyara 85,6 kbit / s, Max.ikojọpọ iyara 42.8 kbit / s, atilẹyin TCP/IP, FTP ati HTTP Ilana.
Ibi ti ina elekitiriki ti nwa
AC ipese agbara
●Foliteji: 85 ~ 264VAC;
●Igbohunsafẹfẹ: 47 ~ 63Hz;
●Agbara: ≤8W
Batiri
●Foliteji: 6VDC
●Agbara: pinnu nipasẹ lemọlemọfún ṣiṣẹ akoko ti batiri
●Batiri ibamu
Electrostatic itujade ajesara | Kilasi 4:GB/T 17626.2 |
Redio-igbohunsafẹfẹ elekitiro-oofa aaye Ìtọjú ajesara | Kilasi 3:GB/T 17626.3 |
Electric fast tionkojalo / ti nwaye ajesara | Kilasi 4:GB/T 17626.4 |
Ajesara gbaradi | Kilasi 4:GB/T 17626.5 |
Redio-igbohunsafẹfẹ aaye inductive ifọnọhan ajesara | Kilasi 3:GB/T 17626.6 |
Agbara igbohunsafẹfẹ oofa aaye ajesara | Kilasi 5:GB/T 17626.8 |
Pulse aaye oofa ajesara | Kilasi 5:GB/T 17626.9 |
Damping oscillation oofa aaye oofa | Kilasi 5:GB/T 17626.10 |
Iwọn itọkasi:
Q/GDW 11223-2014: Alaye imọ-ẹrọ fun wiwa ipinlẹ fun awọn laini okun foliteji giga
4.1 Wiwa ipinlẹ okun le pin si awọn ẹka meji: wiwa ori ayelujara ati wiwa aisinipo.Ogbologbo pẹlu wiwa infurarẹẹdi, wiwa ilẹ lọwọlọwọ ti apofẹlẹfẹlẹ okun, wiwa idasilẹ apakan, lakoko wiwa aisinipo ni wiwa idasilẹ apakan labẹ oniyipada igbohunsafẹfẹ jara resonant idanwo, wiwa okun oscillation apa kan idasilẹ.
4.2 Awọn ipo wiwa ipinlẹ USB pẹlu idanwo gbogbogbo lori iwọn nla, atunwo lori awọn ifihan agbara ti a fura, idanwo lojutu lori ohun elo aṣiṣe.Ni ọna yii, iṣẹ ṣiṣe deede USB le jẹ ẹri.
4.3 Awọn oṣiṣẹ wiwa yẹ ki o lọ si ikẹkọ imọ-ẹrọ ti wiwa okun ati mu awọn iwe-ẹri kan.
4.4 Ipilẹ ibeere ti ebute infurarẹẹdi Aworan ati ilẹ lọwọlọwọ oluwari tọka si Àfikún A. Ipilẹ ibeere ti ga foliteji apa kan yosita erin, olekenka ga foliteji apa kan yosita erin ati ultrasonic apa kan yosita oluwari tọka si Q/GDW11224-2014.
4.5 Ibiti ohun elo tọka si Tabili 1.
Ọna | Foliteji ite ti USB | Ojuami wiwa bọtini | Àbùkù | Online/aisinipo | Awọn akiyesi |
Aworan infurarẹẹdi gbona | 35kV ati loke | Ebute, asopo | Isopọ ti ko dara, tutu, abawọn idabobo | Online | dandan |
Irin apofẹlẹfẹlẹ ilẹ lọwọlọwọ | 110kV ati loke | Eto ilẹ | Aṣiṣe idabobo | Online | dandan |
Ilọjade apa kan igbohunsafẹfẹ giga | 110kV ati loke | Ebute, asopo | Aṣiṣe idabobo | Online | dandan |
Ilọjade apa kan igbohunsafẹfẹ giga giga | 110kV ati loke | Ebute, asopo | Aṣiṣe idabobo | Online | iyan |
Ultrasonic igbi | 110kV ati loke | Ebute, asopo | Aṣiṣe idabobo | Online | iyan |
Idasile apa kan labẹ oniyipada igbohunsafẹfẹ jara resonant igbeyewo | 110kV ati loke | Ebute, asopo | Aṣiṣe idabobo | Aisinipo | dandan |
OWTS oscillation USB apa kan idasilẹ | 35kV | Ebute, asopo | Aṣiṣe idabobo | Aisinipo | dandan |
Tabili 1
Iwọn foliteji | Akoko | Awọn akiyesi |
110(66)kV | 1. Laarin osu 1 lẹhin isẹ tabi atunṣe pataki 2. Lekan fun osu 3 miiran 3. Ti o ba beere | 1. Akoko wiwa yẹ ki o kuru nigbati ẹru nla ba wa lori awọn laini okun tabi lakoko oke ooru. 2. Wiwa yẹ ki o ṣee ṣe nigbagbogbo nigbagbogbo da lori agbegbe iṣẹ buburu, ohun elo ti igba atijọ, ati ẹrọ aibuku. 3. Awọn atunṣe to dara yẹ ki o ṣe da lori awọn ipo ẹrọ ati agbegbe iṣẹ. 4. Eto ibojuwo ori ayelujara ti lọwọlọwọ ilẹ lori apofẹlẹfẹlẹ USB le rọpo wiwa ifiwe rẹ. |
220kV | 1. Laarin osu 1 lẹhin isẹ tabi atunṣe pataki 2. Lekan fun osu 3 miiran 3. Ti o ba beere | |
500kV | 1. Laarin osu 1 lẹhin isẹ tabi atunṣe pataki 2. Lekan fun osu 3 miiran 3. Ti o ba beere |
Tabili 4
5.2.3 Aisan àwárí mu
O jẹ dandan lati darapo fifuye ti okun ati aṣa ajeji lọwọlọwọ ti apofẹlẹfẹlẹ okun pẹlu data wiwọn ti apofẹlẹfẹlẹ okun.
Awọn ibeere iwadii tọka si Tabili 5.
Idanwo | Abajade | Imọran |
Ti gbogbo awọn ibeere ti o wa ni isalẹ ba pade: 1. Idiye iye ti lọwọlọwọ ilẹ.50A; 2. Awọn ipin laarin ilẹ lọwọlọwọ ati fifuye.20%; 3. O pọju.iye / Min.iye ti nikan alakoso ilẹ lọwọlọwọ.3 | Deede | Ṣiṣẹ bi deede |
Ti eyikeyi ibeere ni isalẹ ba pade: 1. 50A≤absolute iye ti ilẹ lọwọlọwọ ≤100A; 2. 20% ≤ ipin laarin lọwọlọwọ ilẹ ati fifuye ≤50%; 3.3≤Max.iye / min.iye ti ilẹ alakoso kan lọwọlọwọ≤5; | Išọra | Mu ibojuwo lagbara ati kuru akoko wiwa |
Ti eyikeyi ibeere ni isalẹ ba pade: 1. Idiye iye ti lọwọlọwọ ilẹ:100A; 2. Awọn ipin ti ilẹ lọwọlọwọ ati fifuye:50%; 3. O pọju.iye / min.iye ti nikan alakoso ilẹ lọwọlọwọ:5 | Àbùkù | Pa agbara ati ṣayẹwo. |
Tabili 5