GDKC-15 Series Circuit Fifọ Oluyanju
Fifọ Circuit foliteji giga jẹ ọkan ninu ohun elo iṣakoso pataki julọ ninu eto agbara.GDKC-15 Series ti lo lati se idanwo awọn ìmúdàgba abuda kan ti ga foliteji Circuit fifọ.O rọrun lati ṣiṣẹ, pẹlu iṣedede giga.
GDKC-15A | GDKC-15B | GDKC-15C | GDKC-15D | GDKC-15E | GDKC-15F | GDKC-15G | GDKC-15H | |
Irin olubasọrọ | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 12 |
Idaduro pipade | 6 | 6 | 6 | 6 | 6 | 6 | 6 | |
Olubasọrọ aworan atọka | 3 | 3 | 3 | 3 | 6 | |||
Ilẹ-ilẹ ti o pari-meji | 3 | 3 | 3 | 6 | ||||
Atako ti o ni agbara (olutako ti a ti fi sii tẹlẹ) | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
Aimi resistance | 1 | 1 | 3 | 3 | 3 | 3 | 6 | |
Ilẹ resistance | 3 | 6 |
●O dara fun idanwo ẹrọ ti gbogbo iru awọn iyipada SF6, awọn ohun elo apapo GIS, awọn iyipada igbale ati awọn iyipada epo.
●Agbara egboogi-kikọlu ti o lagbara.O le ṣe idanwo ni irọrun ati iwọn deede ni ile-iṣẹ 500KV.
●Accelerometer (iyan), sensọ laini, sensọ iyipo, rọrun lati fi sori ẹrọ ati rọrun.
●Gbogbo data ti idanwo abuda ẹrọ ẹrọ yipada ati maapu fọọmu igbi ti o baamu ni a gba lẹhin ti yipada yipada ni ẹẹkan.
●Tọju data idanwo aaye ati aago akoko gidi ti a ṣe sinu, eyiti o rọrun fun fifipamọ ati fifipamọ ọjọ idanwo ati akoko.
●Pẹlu iboju LCD 10.1inch, ṣafihan gbogbo data ati maapu, pẹlu ina lẹhin, atunṣe itansan LCD ati iranti pipa.
●Išišẹ akojọ aṣayan ore, rọrun lati lo.Pẹlu itẹwe ti a ṣe sinu lati tẹjade gbogbo awọn abajade data ni kiakia.
●Ni ipese pẹlu sọfitiwia iṣakoso itupalẹ data, eyiti o le ṣiṣẹ lori ayelujara pẹlu PC, pẹlu faili ọna kika WORD.Awọn abajade idanwo naa le ṣejade si gbogbo iru awọn atẹwe titẹ awọn ijabọ idanwo lati jẹ ki idanwo aaye naa di kọnputa.
●Ṣii ati yiyan iyara isunmọ ati iṣẹ asọye olumulo ti ṣeto ni ibamu si awọn iwulo, o dara fun wiwọn iyara ti eyikeyi iru awọn iyipada.
●Aago:
12 awọn olubasọrọ atorunwa ìmọ (sunmọ) akoko
Ni amuṣiṣẹpọ alakoso
Amuṣiṣẹpọ alakoso-si-alakoso
●Atunse:
CO, OC, akoko COC,
Akoko ṣiṣi akọkọ, akoko isunmọ akọkọ, akoko isunmọ keji, akoko isunmọ, akoko ti o ku, ko si akoko lọwọlọwọ.
●Gbigbe:
Pa akoko agbesoke, awọn akoko, ilana ati igbi ti awọn olubasọrọ kọọkan.
Nsii rebound titobi ti kọọkan olubasọrọ.
Iyara: iyara ni olubasọrọ kan ṣiṣi ati pipade kan, iyara ti o pọju, ọna abuda ti irin-ajo akoko.
Irin-ajo: irin-ajo lapapọ, ijinna ṣiṣi, irin-ajo lori irin-ajo, irin-ajo apọju, titobi isọdọtun.
Lọwọlọwọ: ṣii/sisọ lọwọlọwọ, aworan igbi lọwọlọwọ ti okun ṣiṣi/sisọ.
Foliteji ti n ṣiṣẹ: oni-nọmba DC0 ~ 300V / 20A ti a ṣe sinu, orisun agbara adijositabulu ti fifọ, laifọwọyi pari idanwo iṣẹ LV ti fifọ Circuit ati wiwọn iye foliteji igbese ti olufọ Circuit.
Idaduro pipade: akoko iṣaaju-simẹnti, ipo igbi iṣaaju-pitch ati iye resistance ti resistor pipade ti 6contacts.(aṣayan)
Olubasọrọ Graphite: ṣiṣi, akoko pipade ati ọna igbi agbara ti Siemens graphite olubasọrọ yipada pẹlu awọn olubasọrọ ọna 3 tabi 6. (iyan)
Ilẹ-ilẹ ti o pari-meji: labẹ 3 tabi 6-ọna ilẹ-ibudo meji-ọna, o le ṣe iwọn deede šiši ati akoko pipade.(aṣayan)
Idaabobo aimi: 1 * 100A wiwọn resistance olubasọrọ.
Atako ti o ni agbara (olutasi-iṣaaju-iṣaaju): 1 * 100A iyipada igbi ti resistance agbara lakoko iṣẹ fifọ Circuit.
●Ayika Lilo
Agbara titẹ sii: 220V± 10%, 50Hz±10%, Ipa afẹfẹ: 86-106kpa
Iwọn otutu: -10-40℃ Ọriniinitutu: ≤80% RH
●Aabo Performance
Idabobo Resistance>2MΩ
Agbara Dielectric: Ikarahun le ṣe idiwọ foliteji igbohunsafẹfẹ agbara 1.5kV ni iṣẹju 1 laisi filasi ati arcing.
●Awọn paramita Ipilẹ
Aago: Iwọn 20000.0ms, ipinnu 0.01ms, aṣiṣe 0.5%
Idaduro pipade: ibiti 10kΩ, min.ipinnu 1Ω, aṣiṣe 0.5% (aṣayan)
Olubasọrọ aworan atọka: ibiti 200ms, min.ipinnu 0.1ms, aṣiṣe 0.5% (aṣayan)
Ilẹ-ipari-meji: ibiti 200ms, min.ipinnu 0.1ms, aṣiṣe 0.5% (aṣayan)
Idaabobo aimi: ibiti 1uΩ~10mΩ, min.ipinnu 0.01μΩ, aṣiṣe 0.5%
Agbara to lagbara: ibiti 10mΩ, min.ipinnu 1μΩ, aṣiṣe 0.5%
Idanwo lọwọlọwọ: DC 50A, 100A (iwọn ipele 3 ni akoko kanna)
Iyara: Iwọn 20.00m/s ipinnu 0.01m/s aṣiṣe 0.5%
Irin-ajo:
Awọn oriṣi | Ibiti o | Ipinnu | Asise |
Fifọ igbale | 50.0mm | 0.1mm |
0.5% |
SF6 Circuit fifọ | 300.0mm |
1mm | |
EpoOpin Iyika monamona | 600.0mm |
Lọwọlọwọ: ibiti 20.00A, ipinnu 0.01A
Agbara ti njade: DC 0-300V oni adijositabulu / 20A (iṣiṣẹ lẹsẹkẹsẹ), ipinnu 1V.
Awọn iwọn: nipa 360mm (L)* 280mm (W)* 300mm (H)
Iwọn: nipa 10kg
Akọkọunit pẹlu 10,1-inch tabulẹti | 1 pc |
Ẹya ẹrọ miiran | 1 pc |
Ṣaja fun tabulẹti | 1 pc |
American boṣewa ohun ti nmu badọgba | 2 pcs |
Rotari sensọ iyara | 1 pc |
Sensọ iyara laini50mm | 1 pc |
Okun asopọ ifihan iyara (5-mojuto dabobo waya) | 1 pc |
Ṣiṣii ati pipade okun iṣakoso(3-USB sheathed mojuto) | 1 pc |
Ita okunfaṣe iwariokun (pupa/dudu, 2-mojuto) | 1 pc |
Okun ilẹ | 1 pc |
Olubasọrọ okun igbeyewo(4-USB sheathed mojuto) | 1pc |
Contact igbeyewo okun gbooro (5M, ofeefee, alawọ ewe ati pupa kọọkan ọkan-nkan, dudu 3pcs) | 6awọn kọnputa |
Okun kukuru (0.5m dudu,2m dudu) | 2 pcs |
Okùn Iná | 1 pc |
Gbogbo Apapọ ati ipilẹ oofa | 1 ṣeto |
Awọn ẹya ẹrọ fifi sori ẹrọ pataki | 1 ṣeto |
Idanwo awọn agekuru ati awọn thimbles | 18 pcs |
Contact resistance okun igbeyewo(5M) | 1 pc |
Iwe titẹ sita | 2 eerun |
okun USB | 1 pc |
Itọsọna olumulo | 1 pc |
Factory igbeyewo Iroyin | 1 pc |