GDBT-1000kVA Amunawa Igbeyewo ibujoko
Nkan Idanwo:
22.9kV Awọn oluyipada Alakoso Nikan ati awọn Ayirapada pataki,fifuye foliteji ati lọwọlọwọ: AC 0-650V/78A, AC 0-1200V/29A, AC 0-2400V/14.6A
Ikọju ti oluyipada idanwo wa laarin 7%, ẹgbẹ HV jẹ 23kV, 11kV, 6kV.LV ẹgbẹ jẹ 0.05kV-2.4kV.
Ibujoko idanwo yii le ṣe idanwo ni isalẹ:
1. Ko si-fifuye igbeyewo pẹlu ko si-fifuye pipadanu, awọn ogorun ti ko si fifuye lọwọlọwọ to won won lọwọlọwọ.
2. Igbeyewo fifuye pẹlu pipadanu fifuye, iwọn foliteji impedance, iyipada iwọn otutu laifọwọyi ati idanwo pipadanu fifuye labẹ 30% tabi loke kikun lọwọlọwọ.
3. Induced foliteji igbeyewo.
●Afọwọṣe igbasilẹ data idanwo ati fipamọ sinu aaye data.
●Awọn data ti Ko si-fifuye igbeyewo le ti wa ni atunse nipa igbi ati foliteji won won laifọwọyi.
●Awọn data ti Igbeyewo Fifuye le ṣe atunṣe nipasẹ iwọn otutu (75 ℃, 100 ℃, 120 ℃, 145 ℃) ati iwọn lọwọlọwọ.
●Ninu idanwo Ko si fifuye, foliteji ẹgbẹ LV le ṣe abojuto.
●Ninu idanwo fifuye, lọwọlọwọ ẹgbẹ HV le ṣe abojuto.
●Gbogbo awọn iṣẹ idanwo ati ilana idanwo le yan ati iṣakoso nipasẹ awọn bọtini ti nronu iwaju.
●Gbogbo awọn abajade idanwo jẹ atunṣe ni ibamu si ibeere GB1094, IEC60076 tabi ANSI C57.
●Ilana idanwo le tẹsiwaju nipasẹ sọfitiwia PC.
●Gbogbo data le wa ni ipamọ ati tẹjade.
●Pẹlu aabo odo, aabo lọwọlọwọ ati awọn iṣẹ aabo foliteji.
●CT/PT yipada ni aifọwọyi.
●Ibujoko idanwo yoo ṣakoso ni kikun si gbogbo Circuit lupu ati ṣe atẹle wiwọn.
●Eto itaniji aabo.
Ayipada Ayipada ati Ko si-fifuye Oluyẹwo (O kan fun itọkasi, awoṣe ikẹhin jẹ Fluke Norma 4000)
Iwọn foliteji: 0-1000V
Iwọn lọwọlọwọ: 0.25-20A, deede 0.2%.
Agbara deede 0.3%.
Ipin agbara 0.050-1.000, deede 0.3%
Igbohunsafẹfẹ 40-70Hz, deede 0.1%.
Agbara P
Ko si fifuye lọwọlọwọ Io,%
No-fifuye pipadanu Po
fifuye Pk
Impedance foliteji Uk
Agbara Po
Apapọ foliteji ila Un
Apapọ lọwọlọwọ Ni.
HV CT ni pato
Iwọn foliteji: 3kV
Iwọn iwọn: 0.25A-110A
Yiye 0.05%
Ipin awọn iyipada jẹ 100,50,30,20,10,5,2.5/1A
PT ni pato
Iwọn foliteji: 0.1kV-3kV(50Hz-400Hz)
Yiye 0.05%
Ipin awọn iyipada jẹ 3,2,1,0.5kV/0.1kV
Ipese Agbara Igbohunsafẹfẹ Ayipada
Input foliteji: Nikan alakoso AC380V, 60Hz
Iwọn iwọn: 0-800V
Iwọn agbara: 30kVA
Ijade lọwọlọwọ: 0-37.5A
Igbohunsafẹfẹ ijade: 180Hz, 240Hz, 400Hz±2%
Amunawa Agbedemeji
Agbara: 40kVA
Input Foliteji: Nikan alakoso 500V
Foliteji ti njade: 0-650V-1200V-2400V
100kVA Nikan Alakoso Alakoso
Input foliteji: Nikan alakoso 380V / 60Hz, o wu foliteji 20-650V.
O pọju.fifuye lọwọlọwọ: 154A
Kii ṣe ilana olubasọrọ, rọrun lati lo.
Nigbati foliteji titẹ sii jẹ ibakan, o le ṣatunṣe foliteji o wu laisiyonu pẹlu fifuye.O jẹ apẹrẹ nipasẹ ipo igbohunsafẹfẹ 60Hz.
Ibeere apẹrẹ
Gbogbo idanwo ti a beere ni ipese ni ijoko kanna, iṣẹ kọọkan jẹ ominira.Gbogbo idanwo jẹ aifọwọyi.
Idanwo Iwa Ayipada (Ko si fifuye ati Idanwo fifuye)
O jẹ iṣakoso nipasẹ PC ati pe o pese olutọsọna foliteji 100kVA, oluyipada agbedemeji 40kVA.
A le ṣe awọn awoṣe igbelewọn oriṣiriṣi ti o da lori ibeere gangan.